Features: |
|
| Power Input/Out - Model IPS-15M-CE (Master Unit; 230 VAC): | |
| AC Input: | 10 Amps Max. |
| Voltage: | 210 - 240 VAC, 50 Hz |
| Connectors: | IEC-320 Inlets |
| AC Output: | One (1) - Expandable to Five |
| Connectors: | IEC-320-C13 Outlets |
| Current Load: | 10 Amps Total |
| Control / Modem Ports Interface: | |
| Connector: | DB9M, RS232C, DTE (9-to-9-pin, null cable included) |
| Coding: | Serial, 9600 bps, 8 Bits, No Parity |
| Physical / Environmental: | |
| Size: |
Height: 1.75" (4.5cm) Depth: 7" (17.8cm) Width: 5.80" (14.7 cm) Master Unit / 4.60" (11.7 cm) Satellite Unit |
| Shipping Weight: | 4 lbs. Shipping Weight |
| Temperature: | (Operating) 32oF to 122oF (0oC to 50oC) |
| Humidity: | 10 to 90% RH |
| Agency Approvals: | CE Approval |
| Ordering Inforamtion: | |
| IPS-15M-CE | Master Control Unit, 230 VAC @ 10 Amps |
| IPS-15S-CE | Satellite Unit, 230 VAC @ 10 Amps |
| IPS-15R | 19" Rack Mount Tray, 1RU (Mounts Master Unit and Two Satellite Units) |
| IPS-15ZU | Mounting Bracket for Zero unit Mounting |
|
Two Convenient User Interfaces The IPS-15-CE provides two convenient methods for accessing configuration and switching functions; The Web Browser Interface and the Command Line Interface. The Web Browser Interface consists of a series of simple, easy-to-use web page menus that allow you to select configuration parameters or initiate switching operations using your TCP/IP network and a JavaScript enabled web browser. The Command Line Interface is an ASCII menu system, which allows you to configure and operate the IPS-15-CE via telnet over TCP/IP network, via modem connection or via local PC using a terminal program such as Hyperterminal or TeraTerm. |
|
|
Security Features Access to the IPS-15-CE command mode is password protected to prevent unauthorized users from gaining access to sensitive switching and configuration functions. Both the Web Browser Interface and Command Line Interface require the user to enter a password before allowing access. Passwords transmitted via web browser use 64-bit encryption techniques to ensure that passwords remain protected and access to your equipment remains secure. Telnet control can be user-defined to a discrete TCP port, or completely turned off to ensure that no unprotected port is present. The IPS-15-CE also features two different levels of operational passwords; the System Administrator Level and the User Level. The System Level provides access to all configuration and switching functions, while the User Level is limited to switching functions only. Easy to Configure, Easy to Use The IPS can be configured via network, via modem, or locally via the serial console port. Easy to master, user-friendly menus and commands let you assign a location name, set system parameters and view plug status. Outlets can be switched On, Off, or booted using plug numbers or names. |
|
| Quantum Data Systems (H.K.) Ltd. |